First Cable Products

H07V-K



Application

This cable is suitable for permananet installation in conduit and as wiring of switchboard cabinet

Construction 

Bare copper conductor,fine wire stranded to IEC 60228,class 5
PVC insulated to IEC 60227
Available in various colours


Electrical & Technical Data

Working voltage Uo/U : 450/750V
Test voltage : 2500 V
Working temperature : -50C to +700C
Minimum Bending radius : 4 x  cable diameter
Flame retardancy     : IEC-60332-1




Cross section


Outer Diameter
approx

Cable Weight
approx
DC Resistance at 20°C
Conductor
(Max)
Insulation Thickness

Current-Carrying Capacity at 30°C

(in air)

(Max)

Conductor Make-up

Short circuit current at 1 sec

 

Max

(mm2)(mm)(kg/km)(Ω/km) (mm)(A)(No of wires x diameter(A)
1.5 3,1 21,6 13,30 0,7 24 30 x 0,25 173
2,5 3,7 32 7,980 0,8 32 50 x 0,25 288
4 4,3 49,5 4,950 0,8 41 56 x 0,30 460
6 4,9 69 3,300 0,8 53 84 x 0,30 690
10 6,3 116 1,410 1 72 80 x 0,40 1150
16 7,4 175 1,210 1 97 126 x 0,40 1840
25 9,1 270 0,780 1,2 128 196 x 0,40 2875
35 10,5 371 0,554 1,2 156 276 x 0,40 4025
50 12,4 527 0,386 1,4 195 396 x 0,40 5750
70 14,1 716 0,272 1,4 243 360 x 0,50 8050
95 16,3 969 0,206 1,6 285 475 x 0,50 10925
120 17,9 1208 0,161 1,6 342 608 x 0,50 13800
150 20 1508 0,129 1,8 386 756 x 0,50 17250
185 22,2 1860 0,106 2 441 925 x 0,50 21275
240 25,1 2403 0,0801 2,2 520 1221 x 0,50 27600
300 28 3003 0,0641 2,4 605 1530 x 0,50 34500
400 32 3972 0,0486 2,6 725 2035 x 0,50 41200